Sample condition survey
A spreadsheet example covering main plant, distribution and room terminals. Read across each row from the finding to the proposed action.
Scroll across for risk and remedial actions ↔
| Element / description | Condition | Defects / evidence | Failure likelihood | Failure consequence | Remedial action / verification |
|---|---|---|---|---|---|
B-01Heating boiler Plant roomSole heating boiler. | Poor | Recurring lockouts; condensate connection corroded. Basis: Visual + fault log; combustion not tested. | High Further lockouts likely. | High Building heating lost; no standby. | Plan replacement Investigate faults; confirm duty and replacement need. Check: Commissioning, controls and connections. |
AHU-01Air-handling unit Roof plantBelt-driven office supply. | Fair | Loaded filters; worn drive belt. Basis: Visual only; airflow not measured. | Medium Belt failure / reduced airflow. | Medium Office ventilation reduced or lost. | Service Renew filters and belt; check alignment. Check: Airflow, filter pressure drop and controls. |
P-01Heating pump Plant roomDuty circulation pump. | Poor | Seal seepage; bearing noise. Basis: Running observation; duty not measured. | High Leakage and wear may worsen. | High Heating circulation lost; no standby. | Replace Confirm duty; replace at agreed shutdown. Check: Circulation, controls, leaks and vibration. |
EF-01Extract fan Ceiling voidServed rooms unverified. | Not assessed | No safe access; condition unverified. Basis: Not inspected or functionally tested. | Unknown Insufficient evidence. | Unknown Served areas and critical duty unverified. | Inspect Provide safe access; identify duty and test. Check: Served rooms, airflow and defects; reassess. |
D-01Supply ductwork Ceiling voidInsulated supply branch. | Fair | Torn insulation; open joint seal. Basis: Accessible section only; leakage not tested. | Low Further loss of airflow. | Medium Reduced airflow; energy loss and possible condensation. | Repair Seal joints; reinstate insulation / vapour seal. Check: Repair quality; airflow / leakage as needed. |
V-01Isolation valve RiserHeating branch isolation. | Poor | Seized spindle; valve will not close. Basis: Attempted operation unsuccessful. | Already failed Isolation function unavailable. | Medium No local isolation for maintenance or leaks. | Replace Replace at agreed system shutdown. Check: Full travel, safe isolation test and label. |
FCU-01Fan-coil unit Meeting roomCooling terminal + drain. | Fair | Fouled coil; debris in drain tray. Basis: Visual only; cooling / drainage not tested. | Medium Reduced output / blocked drain. | Medium Local discomfort; water damage if tray overflows. | Service Clean coil, tray and drain. Check: Drainage, fan, controls and leaks. |
RAD-01Radiator OfficePanel radiator + valve. | Good | Minor paint damage; no visible leak. Basis: Visual only; output / valve not tested. | Low Loss-of-output scenario. | Low Local discomfort; a leak could have wider impact. | Maintain Repair finish; retain routine checks. Check: Valve response, heating output and leaks. |
Fictional example. Likelihood is qualitative over 12 months, not a calculated probability. Unknown and failed functions are shown separately. Assess ratings and actions for each project.